What are the Differences Between IEC Power Supply Protection Classes?

The International Electrotechnical Commission (IEC) defines three main classes for power supplies: Class I, Class II, and Class III. In this article from CUI Inc, understand the definitions for each of these classes and how to stay compliant.

These three classes are used to identify different methods for preventing the user of the power supply from being subjected to hazardous voltages from the input power source. Although it is easy to understand the differences in the IEC classes, many engineers are not familiar with the definitions and thus this article will present a quick explanation of the differences between the classes.

  • 1.  Class I - a layer of basic insulation and a grounded conductive chassis
  • 2.  Class II - double insulation (basic + supplemental) or reinforced insulation
  • 3.  Class III - no protection needed as the input voltage is not hazardous

Class I Power Supplies

In IEC Class I power supplies the user is protected from hazardous input voltage levels by at least a layer of basic insulation and a grounded conductive chassis. The first level of safety protection is provided by basic insulation. The second level of safety protection is provided by the grounded conductive chassis. If there is a failure of the basic insulation, then any conductor with a hazardous voltage will be grounded by the conductive chassis before the hazardous voltage can come in contact with the user. All Class I power supplies must have safety ground brought to an electrically conductive chassis in the power supply.


Body-Image 1-CUI-Inc-Differences-Between-IEC-Power-Supply-Protection-Classes

Class II Power Supplies

In IEC Class II power supplies the user is protected from hazardous input voltage levels by at least a layer of basic insulation and a layer of supplemental insulation or a layer of reinforced insulation. For double insulation, the first level of safety protection is provided by the basic insulation while the second level of safety protection is provided by the layer of supplemental insulation. Reinforced insulation provides the same safety factor as the combined basic and supplemental layers of insulation but in a single layer of insulation.

Because of double or reinforced insulation, IEC Class II power supplies are not required to have the safety ground conductor brought to the power supply.


Body-Image 2-CUI-Inc-Differences-Between-IEC-Power-Supply-Protection-Classes

Class III Power Supplies

In IEC Class III power supplies the input voltage is not at a hazardous level and thus the user does not need to be protected from the input voltage. The IEC label for the non-hazardous input voltage is Safety Extra Low Voltage (SELV). The voltage in accessible parts of SELV circuits shall not exceed 42.4 Vac peak or 60 Vdc for longer than 200 ms., with an absolute limit of 71 Vac peak or 120 Vdc. SELV circuits must be separated from hazardous voltages by two levels of protection. The two layers of protection may be basic and supplemental insulation, reinforced insulation, or basic insulation combined with a safety grounded electrically conductive chassis.


Body-Image 3-CUI-Inc-Differences-Between-IEC-Power-Supply-Protection-Classes

Understanding the three IEC Power Supply Protection Classes enables those specifying or selecting power supplies to choose the appropriate class of supply based upon safety, regulatory, and cost constraints.

 

최신 뉴스

Sorry, your filter selection returned no results.

개인정보 보호정책이 업데이트되었습니다. 잠시 시간을 내어 변경사항을 검토하시기 바랍니다. 동의를 클릭하면 Arrow Electronics 개인정보 보호정책 및 이용 조건에 동의하는 것입니다.

당사의 웹사이트에서는 사용자의 경험 향상과 사이트 개선을 위해 사용자의 기기에 쿠키를 저장합니다. 당사에서 사용하는 쿠키 및 쿠키 비활성화 방법에 대해 자세히 알아보십시오. 쿠키와 추적 기술은 마케팅 목적으로 사용될 수 있습니다. '동의'를 클릭하면 기기에 쿠키를 배치하고 추적 기술을 사용하는 데 동의하는 것입니다. 쿠키 및 추적 기술을 해제하는 방법에 대한 자세한 내용과 지침을 알아보려면 아래의 '자세히 알아보기'를 클릭하십시오. 쿠키 및 추적 기술 수락은 사용자의 자발적 선택이지만, 웹사이트가 제대로 작동하지 않을 수 있으며 사용자와 관련이 적은 광고가 표시될 수 있습니다. Arrow는 사용자의 개인정보를 존중합니다. 여기에서 당사의 개인정보 보호정책을 읽을 수 있습니다.